The whole installation as designed: the heat source, the refrigerant circuit and the heating circuit, with the temperatures, pressures, flows and powers at the design point. The dashed frame is what sits in the heat pump unit.
The cycle on the refrigerant's pressure–enthalpy chart. Inside the dome the refrigerant boils or condenses at constant temperature; the horizontal lengths are the energy per kilogram: heat taken from the source (4→1), compressor work (1→2) and heat delivered (2→3).
The same cycle on the temperature–entropy chart, with the heat source and the heating circuit. The gaps between the refrigerant and the water or air are what the heat exchangers need to work; every kelvin of gap costs COP.
Temperatures along each heat exchanger, against the heat transferred. The refrigerant must stay hotter than the water in the condenser and colder than the source in the evaporator everywhere — the smallest gap is the pinch.
Condenser
Evaporator
Where the delivered heat comes from: most of it is taken from the source for free; the compressor adds the rest as electrical work.
The design point is the coldest hour; the year is mostly milder. For every degree of outdoor temperature, the bars count the hours a year it occurs at this location; the heat pump follows the building's load, more efficiently on mild days, and an electric heater covers what it cannot. Below the balance point the heat pump alone is not enough.
Heat load and heat pump capacity
Heat delivered over the year, by outdoor temperature
Running costs and CO₂ per year
Bin method after EN 14825: load linear from the design temperature to the heating limit, inverter down to 30 % of full capacity, on/off cycling below it (Cd 0.9), defrost losses up to 10 % around +1 °C for air sources. Hourly temperatures 2015–2024 from the Open-Meteo historical weather API (ERA5 reanalysis, CC BY 4.0). Gas CO₂ 0.202 kg/kWh.
Every refrigerant at the same source, heating circuit and compressor settings. Click a row to use that refrigerant.
Cycle states
Components
Refrigerant properties from CoolProp. Pressure drops in pipes and heat exchangers are neglected. U-values, volumetric efficiencies, the charge estimate and the borehole guide values (after VDI 4640) are typical figures for a first design, not a replacement for manufacturers' data.